6-9 Advanced Settings (Connection, Communication Cycle Time, Slave Function
Settings, Etc.)
6-9-2 Communication Cycle Time Settings
Note
•
Both COS and Cyclic settings cannot be made at the same time.
•
If
Poll
and
COS
settings or
Poll
and
Cyclic
settings are used in combination, check
that the output settings of the both connections are the same.
•
The automatic allocation function is not possible for devices if the user already made
connections settings for the devices with the advanced setup. 3. Unregister and
register the devices so that the automatic allocation function will be available for the
devices.
6-9-2 Communication
Cycle Time Settings
Component - Parameter - Edit - Communication Cycle Time Tab
Note: This procedure is the same for the CS1W-DRM21(-V1), CJ1W-DRM21,
CVM1-DRM21-V1, and C200HW-DRM21-V1.
It is possible to set the communication cycle time on the Communication Cycle Time
Tab Page. Furthermore, it is possible to check the present communication time
calculated from the registered device information.
The following dialog box will be displayed by clicking on the Communication Cycle
Time Tab.
Set the communication cycle time between 1 and 500 ms. To set the communication
cycle time automatically, click the
Default Setup
Button or set the communication
cycle time to 0 ms.
The communication cycle time set will be automatically calculated and displayed
according to the registered device information and the baud rate.
6-38
Summary of Contents for CX-INTEGRATOR - V1.1
Page 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Page 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Page 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Page 328: ...Appendices A...
Page 336: ......