3-2 Setting the Routing Tables
3-2-2 Creating the FINS Local Routing Tables
3-2-2
Creating the FINS Local Routing Tables
This section shows how to set the routing tables (FINS local routing tables) for PLC1,
which is connected directly to the CX-Integrator.
Online Operations
Creating the Local Network Table Online
Create PLC1's local network table online.
1. Verify that PLC1 is
connected
directly to the CX-Integrator and select
Tools – Start
Routing
Table.
Alternately,
right-click the Communications Unit or Port in the Online Connection
Information Window select
Start Routing Table
from the popup menu.
2. The PLC Routing Table Window will be displayed in the Main View format.
3. Click the
Table View
Tab at the bottom of the PLC Routing Table Window to switch
to the Table View format.
3-10