2-2
Connecting Online to the Relay PLC
2-2-2 Procedures
Field name on
Network Tab Page
Item
Contents
Settings
FINS Source
Address
Network
Set the network address of the Ethernet network
connected to the computer.
1 to 127
Use the default setting of 0
if there is only one Ethernet
Unit in the PLC and only
one network is being used.
Network
Set the network address of the Ethernet network
connected to the PLC to which the connected
Ethernet Unit is mounted.
1 to 127
Use the default setting of 0
if there is only one Ethernet
Unit in the PLC and only
one network is being used.
Node
Set the node address of the connected Ethernet
Unit.
Set the node address set on the rotary switches
on the Ethernet Unit.
1 to 254
Frame
Length
Set the maximum frame length.
Do not change the default setting.
CS/CJ-series PLCs: 2,000
bytes
CVM1/CV-series PLCs:
1,950 bytes
FINS Destination
Address
Response
Timeout
This is the timeout time for receiving a response.
Increase this setting only if there are many
communications errors.
2 s
Click the
Driver
Tab and set the following settings as required.
Select whether FINS node addresses are to be automatically generated
from IP addresses on the computer. This option is selected by default.
Set the IP address of the connected
Ethernet Unit.
Set the UDP port number.
Normally, the default value of 9600 is used.
Clear this selection to enable using an IP address
table or combined method.
Set the computer’s IP address according to the IP
address table.
2-17
Summary of Contents for CX-INTEGRATOR - V1.1
Page 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Page 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Page 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Page 328: ...Appendices A...
Page 336: ......