4-3
Manually Setting Data Links
4-3-3 System
Configuration Example
4-3-3 System
Configuration Example
The procedure is described below, from data link creation through startup, taking a
Controller Link data link system as an example.
CX-Integrator
Controller Link network
CS1G-CPU45
Peripheral Bus or Host Link
Data link
CS1G-CPU45
CS1G-CPU45
1 2
3
Data link
PLC type
Node address
Data Link Setup Example
Area 2
Send
(#1)
Receive
(#2)
Receive
(#3)
DM500
DM530
DM560
DM600
Node 1
Send
(#2)
Receive
(#1)
Receive
(#3)
Node 2
Send
(#3)
Receive
(#1)
Receive
(#2)
Node 3
DM600
DM630
DM660
DM700
DM730
DM760
Area 1
Send
(#1)
Receive
(#2)
Receive
(#3)
CIO 1000
CIO 1030
CIO 1060
CIO 1100
Node 1
CS1G
Send
(#2)
Receive
(#1)
Receive
(#3)
Node 2
CS1G
Send
(#3)
Receive
(#1)
Receive
(#2)
Node 3
C200HX
CIO 1200
CIO 1230
CIO 1300
IR 300
IR 320
IR 350
IR 390
CIO 1260
Size
20 words
Offset
10 words
DM700
DM800
The refresh sequence for nodes 1 and 2 is as follows: #1, #2, #3. For node 3, the
order is #2, #1, #3. Node address 03 does not receive all of the data sent from node
address 02. Rather, data from the 20 words (CIO 1240 to CIO 1259) beginning from
the start a10 words (i.e., the offset) is received in IR 300 to IR 319. Other
data is received with no offset.
4-11
Summary of Contents for CX-INTEGRATOR - V1.1
Page 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Page 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Page 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Page 328: ...Appendices A...
Page 336: ......