24
Data Areas for PC Link Systems
Section 2-5
CPU Bus Unit Flags
and Control Bits
Since the PC Link Unit is a CPU Bus Unit, the following Auxiliary Area flags
and control bits are used to indicate status or control operation of the Unit.
Word
Bit(s)
Name
Function
A001 00 to 15 CPU Bus Unit Restart Bits
These bits can be turned ON to reset the corresponding CPU Bus Units.
The Restart Bits are turned OFF automatically when restarting is com-
pleted. (Bits 00 to 15 correspond to unit numbers 0 to 15.)
A015 00 to 15 CPU Bus Service Disable
Bits
These bits can be turned ON to stop service to the corresponding CPU
Bus Units. (Bits 00 to 15 correspond to unit numbers 0 to 15.)
Turn the bit OFF again to resume service to the CPU Bus Unit.
A302 00 to 15
CPU Bus Unit Initializing
Flags
ON while the corresponding CPU Bus Units are initializing. (Bits 00 to 15
correspond to unit numbers 0 to 15.)
A401 12
CPU Bus Error Flag
ON when an error occurs during the transmission of data over the CPU
bus, or a WDT (watchdog timer) error occurs in a CPU Bus Unit. The unit
numbers of the affected CPU Bus Units are indicated in word A405.
A401 13
Duplication Error Flag
ON when two Racks are assigned the same rack number, two CPU Bus
Units are assigned the same unit number, or the same words are allocated
to more than one Rack or Unit in the PC Setup. The unit numbers of the
affected CPU Bus Units are indicated in word A410.
A402 03
CPU Bus Unit Setting Error
Flag
ON when the CPU Bus Units actually installed differ from the Units regis-
tered in the I/O table. The unit numbers of the affected CPU Bus Units are
indicated in word A427.
A402 07
CPU Bus Unit Error Flag
ON when an error occurs during the transmission of data between the PLC
and CPU Bus Unit. The unit numbers of the affected CPU Bus Units are
indicated in word A422.
A405 00 to 15
CPU Bus Error Unit Num-
ber
ON when an error occurs during the transmission of data over the CPU
bus, or a WDT (watchdog timer) error occurs in a CPU Bus Unit. (Bits 00 to
15 correspond to unit numbers 0 to 15.)
A410 00 to 15
CPU Bus Unit Duplicate
Number
ON when two CPU Bus Units are assigned the same unit number. (Bits 00
to 15 correspond to unit numbers 0 to 15.)
A422 00 to 15
CPU Bus Unit Error Unit
Number
ON when an error occurs during the transmission of data between the PLC
and CPU Bus Unit. (Bits 00 to 15 correspond to unit numbers 0 to 15.)
A427 00 to 15
CPU Bus Unit Setting Error
Unit Number
ON when the CPU Bus Units actually installed differ from the Units regis-
tered in the I/O table. (Bits 00 to 15 correspond to unit numbers 0 to 15.)
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...