70
Troubleshooting with LED Indicators
Section 5-1
Lit
Not lit
---
Lit
Lit
Not lit
Local node is the polling node
(node 0):
Cables are disconnected or con-
nected incorrectly.
Check the Terminating Resistance
switch setting.
Check the cable connections and fix
or replace the cable if necessary.
Local node is the polling node
(node 0):
There are no other nodes in the
PC Link.
Set up the network with at least two
functioning nodes.
The PC Link Unit is set incorrectly. Check whether there is another node
in the PC Link with the same node
address.
Check whether the level/link number
setting is correct.
Lit
Not lit
---
Not lit
Not lit Not lit
Local node is a polled node:
Cables are disconnected or con-
nected incorrectly.
Check the Terminating Resistance
switch setting.
Check the cable connections and fix
or replace the cable if necessary.
Local node is a polled node:
There are no other nodes in the
PC Link.
Set up the network with at least two
functioning nodes.
The PC Link Unit is set incorrectly. Check whether there is another node
in the PC Link with the same node
address.
Check whether the level/link number
setting is correct.
Lit
Lit
Not lit Not lit
Not lit Not lit
The PC Link Unit is faulty or an
error occurred in the PC Link Unit
so that it can’t communicate prop-
erly.
Mount the Unit in another CPU Rack
and replace the Unit if the Error
recurs.
Lit
Lit
---
Not lit
Not lit Not lit
The node address is set outside of
the allowed range.
Set the node address within the fol-
lowing ranges.
Single-level: 00 to 31
Multi-level: 00 to 15
Lit
Flash-
ing
---
Lit
Lit
Not lit
A polled node’s (another node’s)
cables are disconnected or con-
nected incorrectly.
Check the Terminating Resistance
switch setting.
Check the cable connections and fix
or replace the cable if necessary.
An error occurred in communica-
tions with a polled node (another
node).
If noise is causing errors, check and
correct the operating environment.
Separate the communications cables
from power/high voltage lines.
Power is not being supplied prop-
erly to the CPU Unit of a polled
node (another node).
Check the power supply voltage and
supply the proper power.
The PC Link Unit is set incorrectly. Check whether there is another node
in the PC Link with the same node
address.
Check whether the level/link number
setting is correct.
Indicator status
Probable cause
Remedy
RUN
ERC
ERH
LINK0 THIS OTHER
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...