34
PC Link Unit Replacement Procedure
Section 3-2
3-2
PC Link Unit Replacement Procedure
The following table outlines the procedures and precautions for replacement
of PC Link Units.
Item
Unit or setting
Description
Reference
CPU Rack
replacement
CPU Unit (C500, C1000H, or
C2000H)
CPU Backplane
Power Supply Unit
Replace with CVM1/CV-series compo-
nents.
CV-Series Programmable
Controllers Installation Guide
(W195-E1-5)
I/O Units
Special I/O Units
Some can be used in the CVM1/CV
Series.
SYSMAC LINK Units
Host Link Units
Replace with CVM1/CV-series compo-
nents.
PC Link Units
Replace with CVM1-LK401.
3-3 CVM1-LK401 Switch Set-
tings
PC Link Unit
settings
CPU Bus Unit unit number
setting
The unit number must be set since the
CVM1-LK401 is a CPU Bus Unit.
Node address setting
Match the CVM1-LK401’s settings to
the settings of the C500-LK009-V1
Units in the PC Link.
(One exception is the LK003 mode,
which cannot be used. In this case,
change the C500-LK009-V1 Units’
settings.)
3-3-2 Setting the Node
Address in the PC Link
Number of LR bits setting
3-3-3 Setting the Number of
LR Bits (Max. Number of PC
Link Units)
Operating level/Link number
setting
3-3-4 Setting the Level/Link
Number
Transmission line setting (two-
wire or four-wire method)
3-3-5 Setting the Transmis-
sion Line and Terminating
Resistance
Terminating resistance
Number of I/O points to
refresh
These settings are not set in the
CVM1-LK401.
---
Single/Double Unit allocation
Precautions
when writing
ladder program
LR Area words used in PC
Link
Replace LR 00 to LR 63 addresses
with CIO 1000 to CIO 1063.
PLC Run and PC Link Error
Flags
Replace SR 247 to SR 250 bit
addresses with CIO 1500 + 25
×
N to
CIO 1500 + 25
×
N +3 (N = unit num-
ber).
Level Flags
Replace AR 2411 and AR 2412 bit
addresses with bits 11 and 12 of CIO
1500 + 25
×
N +4 (N = unit number).
CPU Bus Unit status area
In the CVM1/CV Series, the status of
the CVM1-LK401 can be monitored
from the ladder program.
3-4-4 CPU Bus Unit Status
Flags
PLC CPU Unit
settings
Setting the PLC’s operation
mode (synchronous/asyn-
chronous operation)
We recommend using synchronous
operation.
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...