13
Installing PC Link Units
Section 2-2
• In a single-level system, just one PC Link Unit can be mounted in a PLC.
In a multi-level system, up to two PC Link Units can be mounted in a PLC.
• When mounting other CPU Bus Units, do not exceed the maximum of 16
CPU Bus Units per PLC.
Note
Tighten the PLC Backplane mounting screws to a torque of 1.2 N
⋅
m and
tighten the Unit securing screws to a torque of 0.9 N
⋅
m.
Number of PC Link
Units per PLC
In a single-level system, one PC Link Unit can be mounted in a CVM1/CV
Series PLC. In a multi-level system, two PC Link Units can be mounted.
Note
The PC Link Units will not detect an error even if two PC Link Units with con-
flicting operating level settings (one or both single-level, both multi-level link
#0, or both multi-level link #0) are mounted in the same PLC. To be sure that
the PC Link operates properly, verify that the level settings are correct.
One PC Link Unit set for single-level operation can be mounted in a single
PLC, or two Units set for multi-level operation (one set to Link #0 and the other
set to Link #1).
CVM1/CV Series
1) CPU Rack
Can be mounted.
CVM1/CV Series
1) CPU Rack
CVM1/CV Series
1) CPU Rack
Can be mounted.
Can be mounted.
2) Expansion
CPU Rack
Cannot be
mounted in
Expansion
I/O Rack.
Cannot be mounted in
Expansion I/O Rack.
Can be mounted.
Cannot be mounted in
Expansion I/O Rac
k.
Level setting
Number of PC
Link Units
Remarks
Single-level
Just one Unit
---
Multi-level
One or two Units
Set one level as Link #0 and the other as Link
#1. If a PC Link Unit is set to single-level oper-
ation, it cannot be mounted in the same PLC
with another PC Link Unit.
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...