Cable Length and Terminating Resistance Settings
Section 2-4
Max. Cable Length
• Electrical (copper) cable length
The total length of the electrical cables in the PC Link system can be up to
500 m. (Individual branch lines can be up to 10 m long.)
• Optical fiber cable length
If the distance between PLCs exceeds 800 m, use a 3G2A9-AL005-(P)E
or 3G2A9-AL006-(P)E Link Adapter. For details, refer to the C
-Series Link
Adapters Installation Guide
(W123-E1-3).
(The 3G2A9-AL005-(P)E and 3G2A9-AL006-(P)E Link Adapters are no
longer being manufactured.)
Setting the
Terminating
Resistance Switch
(TER Switch)
The basic structure of the PC Link operating level has a main line with extend-
ing branch lines. The Terminating Resistance is turned ON on the two PC Link
Units at the ends of the main line in each PC Link operating level. The Termi-
nating Resistance is turned OFF on all other PC Link Units in the system.
Cable type
Link Adapter model
3G2A9-AL002-PE
3G2A9-AL004-PE
3G2A9-AL002-E
3G2A9-AL004-E
APF (All Plastic Fiber optic cable)
20 m
Cannot be used.
PCF (Plastic Clad Fiber optic cable) 200 m
800 m
WIRE
4
↔
2
TER
ON
↔
OFF
PC LINK
Terminating Resistance Setting Switch
Transmission Line Selector Switch
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...