53
Replacement Checklists
Section 3-6
Checklist 3
Use the following checklist when replacing a 3G2A5-LK009 or C500-LK009-
V1 in single-level LK003 mode with a C500-LK009-V1 in single-level LK009
mode.
Terminating
Resistance
Check pin 1 of rear-panel
switch:
[
1(ON
)0 (OFF)]
Pin 1 of SW3: Set the same terminator set-
ting as set on the 3G2A5-LK003-E.
---
1
Terminator con-
nected.
1
Terminator connected.
0
Terminator not
connected.
0
Terminator not connected.
LR Area
LR 00 to LR 31
LR 00 to LR 31
The C500-LK009-V1 is
set to single-level LK009
mode, so the level #1
flags and control bits are
not used.
PC Link Error
and PLC Run
Flags
SR 62
SR 62
Level Flags
Not applicable.
Level #1
AR 2411
Single-level or level #0
AR 2412
PC Link Unit
Restart Bits
SR 6014
Level #1
SR 6010
Single-level or level #0
SR 6014
Item
Original Unit: 3G2A5-LK003-E
Replacement Unit: C500-LK009-V1
Remarks
Item
Original Unit: 3G2A5-LK009/
C500-LK009-V1
Replacement Unit: C500-LK009-V1
Remarks
Node address
Check setting on pins 1 to 5: [ ] Set the node address to the same
one set on the original Unit.
When the CPU Unit is a C500
model, set the C500-LK009-
V1’s node address in the 0 to
7 range.
Check the node address set-
tings on other nodes in the PC
Link to confirm that the same
address is not already taken.
A Unit error will
not
be
detected if the same node
address is set on two PC Link
Units in the same PC Link, but
there will be data errors in the
LR Area.
Pins 1 to 5 Node address
Pins 1 to 5 Node address
00000
0
00000
0
00001
1
00001
1
00010
2
00010
2
00011
3
00011
3
00100
4
00100
4
00101
5
00101
5
00110
6
00110
6
00111
7
00111
7
When a C500 PLC is being used,
the node address setting range is
0 to 7.
When a C500 PLC is being used, the
node address setting range is 0 to 7.
Do not set a node address higher
than 7.
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...