57
Replacement Checklists
Section 3-6
Number of
LR Bits
Check setting on pins 6 to 8:
[
] Bits / [ ] Units
Set the same number of LR bits that
was set on the 3G2A5-LK009/C500-
LK009-V1.
Make the “number of LR bits”
setting on the polling node
(node 0) in the PC Link. The
“number of LR bits” settings
on the other nodes (polled
nodes) are ignored.
When a C500 PLC is replaced
with a CVM1/CV-series PLC,
the maximum number of Units
is double the original value for
the same number of LR bits,
because the LR Area is twice
as large.
In pattern B, the original
3G2A5-LK009/C500-LK009-
V1 is set to single-level LK003
mode.
Set the level/link number (next
item in table) to single-level
mode.
Note
:
Settings 011 to 111 are invalid
settings in the C500-LK009-
V1, but the number of LR bits
will be set to 64 bits/8 Units if
the setting is in the invalid
range.
Pins 6 to 8
Single-level LK003
mode
Pins 6 to 8
Pin 3 (single-level)
000
256 bits / 2 Units
000
32 bits / 32 Units
001
128 bits / 4 Units
001
64 bits / 16 Units
010
64 bits / 8 Units
010
128 bits / 8 Units
011
64 bits / 8 Units
(See note.)
011
256 bits / 4 Units
100
100
512 bits / 2 Units
101
101
Invalid setting
110
110
111
111
Level/Link
Number
Pins 3 and 4: Check if set to sin-
gle-level LK003 mode (10).
Pins 3 and 4: Set both pins to 1 (sin-
gle-level).
Set the replacement CVM1-
LK401 to single-level mode.
Pins 3 & 4
Level/Link Number
setting
Pins 3 and 4
Level/Link Number
setting
11
Single-level LK009
11
Single-level (Set either
11 or 10.)
10
Single-level LK003
10
01
Multi-level Link #1
01
Multi-level Link #1
00
Multi-level Link #0
00
Multi-level Link #0
Transmission
Line Selector
Check SW2:
[Up (4-wire)
Down (2-wire)]
WIRE switch: Set the same setting as
set on the 3G2A5-LK009/C500-
LK009-V1.
---
Up
4-wire/Use optical
fiber cable.
4 (left)
4-wire/Use optical
fiber cable.
Down
2-wire/Use electrical
cable.
2 (right)
2-wire/Use electrical
cable.
Terminating
Resistance
Check pin 1 of SW3:
[
1(ON
)/0 (OFF)]
TER switch: Set the same setting as
set on the 3G2A5-LK009/C500-
LK009-V1.
---
1
Terminator con-
nected.
ON (left)
Terminator connected.
0
Terminator not con-
nected.
OFF (right)
Terminator not con-
nected.
Item
Original Unit: 3G2A5-LK009/
C500-LK009-V1
Replacement Unit: CVM1-LK401
Remarks
Summary of Contents for CVM1 Series
Page 1: ...Cat No W434 E1 01 SYSMAC CVM1 CV Series CVM1 LK401 PC Link Unit This manual is PDF file only...
Page 2: ...CVM1 LK401 PC Link Unit Operation Manual Produced July 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 41: ...26 Differences from Earlier PC Link Units Section 2 6...
Page 77: ...62 Replacement Checklists Section 3 6...
Page 95: ...80 Link Adapter Specifications Appendix B...
Page 101: ...86 PC Link System I O Response Time Appendix C...
Page 103: ...88 PC Link Settings and Status Areas Appendix D...
Page 105: ...Revision History 90...