41
Initial Settings Data
Section 4-2
4-2
Initial Settings Data
4-2-1
DM Area Allocations and Contents
The initial settings for the ID Sensor Unit are performed using the words allo-
cated to the ID Sensor Unit as a Special I/O Unit in the DM Area.
Note
1.
The words allocated to the ID Sensor Unit in the DM Area are determined
by the setting of the unit number switches on the Unit’s front panel. Set unit
numbers so that the same words are not allocated to more than one Unit.
(Refer to page 39 for the setting method.)
2.
If the same unit number is set for more than one Special I/O Unit, a fatal
error (
No. duplication error
on CX-Programmer or
Unit No. Duplication
on
Programming Console), and the PLC will not operate.
SYSMAC CS-/CJ-series PLC
Special I/O Unit Words in DM Area
Allocated Words
Allocated Words
Unit 0 D20000 to D20099
Unit 1 D20100 to D20199
Unit 2 D20200 to D20299
Unit 3 D20300 to D20399
Unit 4 D20400 to D20499
Unit 5 D20500 to D20599
Unit 6 D20600 to D20699
Unit 7 D20700 to D20799
Unit 8 D20800 to D20899
Unit 9 D20900 to D20999
Unit 10 D21000 to D21099
Unit n
Unit 95 D29500 to D29599
ID Sensor Unit
CS1W-V600C11/CJ1W-V600C11
Initial Settings
System Settings
Auto Wait Time
m
m + 1
SYSMAC CS-/CJ-series PLC
Special I/O Unit Words in DM Area
Unit 0
D20000
to D20199 D20100
to D20299
Unit 1
Unit 2
D20200
to D20399 D20300
to D20499
Unit 3
Unit 4
D20400
to D20599 D20500
to D20699
Unit 5
Unit 6
D20600
to D20799 D20700
to D20899
Unit 7
Unit 8
D20800
to D20999 D20900
to D21099
Unit 9
Unit 10
D21000
to D21199
Unit n
100
×
n to
100
×
n + 99
100
×
n to
100
×
n + 99
Unit 94
D29400 to 29599
ID Sensor Unit
CS1W-V600C12/CJ1W-V600C12
Initial Settings
System Settings
Auto Wait Time
(Not used)
System Settings
Auto Wait Time
(Not used)
m
m + 1
to
m + 100
m + 101
to
(m = 100
×
Unit No.)
(m = 100
×
Unit No.)
Transferred automatically
according to unit
number when power is
turned ON or the Unit
is restarted.
Transferred automatically
according to unit
number when power is
turned ON or the Unit
is restarted.
Summary of Contents for CJ - 12-2004
Page 2: ...SYSMAC CS CJ Series ID Sensor Units Operation Manual Revised December 2004...
Page 3: ...iv...
Page 11: ...xii...
Page 55: ...36 Connections and Wiring Section 3 4...
Page 69: ...50 I O Data Allocations Section 4 3...
Page 91: ...72 Data Check Section 5 7...
Page 141: ...122 Sample Programming Appendix B...
Page 147: ...128 Revision History...