39
Outline of Data Exchange
Section 4-1
4-1-1
Unit Number Setting
The words allocated to the ID Sensor Unit in the Special I/O Unit Area and DM
Area are determined by the unit number setting on the Unit’s front panel.
CS1W-V600C11/C12
CJ1W-V600C11/C12
Note
1.
If the same unit number is set for more than one Special I/O Unit, a fatal
error (
No. duplication error
on CX-Programmer or
Unit No. Duplication
on
Programming Console), and the PLC will not operate.
2.
When a Double-head ID Sensor Unit (CS1W-V600C12,CJ1W-V600C12)
is used, two unit numbers are allocated.
0
1
2
3 4 5 6
7
8
9
0
1
2
3 4 5 6
7
8
9
Switch
No.
Unit
No.
CS1W-V600C11/
CJ1W-V600C11
CS1W-V600C12/
CJ1W-V600C12
Words
allocated in
Special I/O
Unit Area
Words
allocated in
DM Area
Words
allocated in
Special I/O
Unit Area
Words
allocated in
DM Area
0
Unit 0
CIO 2000 to
CIO 2009
D20000 to
D20099
CIO 2000 to
CIO 2019
D20000 to
D20199
1
Unit 1
CIO 2010 to
CIO 2019
D20100 to
D20199
CIO 2010 to
CIO 2029
D20100 to
D20299
:
:
:
:
:
:
94
Unit 94 CIO 2940 to
CIO 2949
D29400 to
D29499
CIO 2940 to
CIO 2959
D29400 to
D29599
95
Unit 95 CIO 2950 to
CIO 2959
D29500 to
D29599
(Cannot be set)
V600
C11
RUN E
RC
ERP E
RH
T/R
NORM/ERR
TEST
ON
0
1 2 3
4
5
6
7
8
9
0
1 2 3
4
5
6
7
8
9
Summary of Contents for CJ - 12-2004
Page 2: ...SYSMAC CS CJ Series ID Sensor Units Operation Manual Revised December 2004...
Page 3: ...iv...
Page 11: ...xii...
Page 55: ...36 Connections and Wiring Section 3 4...
Page 69: ...50 I O Data Allocations Section 4 3...
Page 91: ...72 Data Check Section 5 7...
Page 141: ...122 Sample Programming Appendix B...
Page 147: ...128 Revision History...