98
ID Sensor Unit Alarms
Section 7-2
Note
First word allocated to Unit in CIO Area: n = CIO 2000 + 10
×
unit No.
Word address
Name of alarm
Meaning
Unit response
Correction
Head 1 of
CS1W-
V600C11,
CS1W-
V600C12,
CJ1W-
V600C11,
or CJ1W-
V600C12
Head 2 of
CS1W-
V600C12
or CJ1W-
V600C12
n + 7
n + 17
Bit 15
ID Sensor Unit
CPU error
An error
occurred in the
ID Sensor Unit
when the power
supply was
turned ON or
immediately
after the Unit
was restarted.
Unit operation
will stop.
Turn the power supply OFF and ON or
turn ON the Special I/O Unit Restart Bit
Replace the I/O Sensor Unit if the error
persists even though the Unit is reset.
Bit 12
ID Sensor Unit
memory error
An error
occurred when
memory read
was read.
Unit operation
will stop.
Turn the power supply OFF and ON or
turn ON the Special I/O Unit Restart Bit
Replace the I/O Sensor Unit if the error
persists even though the Unit is reset.