69
DM Area Settings and Functions
Section 7-2
Operating Mode
(Word m Bits 03 to 00)
Set these bits so that the setting will correspond to the MODE switch setting.
Forced External Output
(Word m Bits 04 to 07)
Forced external outputs are enabled or disabled with these bit settings.
External Output Mode
(Word m Bits 11 to 08)
Set these bits so that the setting will correspond to the setting of the rear set-
ting switch.
Data Type
(Word m Bits 15 to 12)
These bits are used to set the counter value, upper limit, and lower limit data
in BCD or hexadecimal.
Counter Input Type
(Word (m+1) or (m+2)
Bits 03 to 00)
Offset phase pulse inputs must be multiplied by 1, 2 or 4.
Reset Mode
(Word (m+1) or (m+2)
Bits 15 to 08)
These bits are used to specify the counter reset mode.
Operating mode
(1: Linear mode; 2: Circular mode)
Forced external output
(0: Disabled; 1: Enabled)
External output mode
(0: NPN; 1 PNP)
Data type (0: BCD; 1: Hexadecimal)
Input types
0: x 1
1: x 2
2: x 4
3: Up and down pulses input
4: Pulse and direction input
Offset phase inputs
Reset mode
(00 to 11 (modes 0 to 11))