98
Program Example for Preset Mode
Section 8-6
Example Settings
Switch Settings
The unit number of the High-speed Counter Unit is set to 1 and the Unit will
have NPN external outputs.
Wiring
The A- and B-phase outputs of the incremental encoder are connected to
counter 1 inputs A and B.
Connect external outputs 0 to 2 to the motor ON, speed (high/low), and brake
input terminals of the motor controller.
Connect external output 3 to the cutter.
DM Settings
Item
Set value
Counter preset value
10,000
(A)
100
(B)
150
(C)
200
(D)
0
(E)
50
(T)
500 ms
Counter preset value
Count value
Motor operation
(External output 0)
Speed (high/low)
(External output 1)
High
Low
Brake
(External output 2)
Cutter
(External output 3)
Preset mode, external NPN outputs, BCD data,
offset phase pulse inputs x 2, and reset mode 0
Preset value = 10000
(A) = 100
(B) = 150
(C) = 200
(D) = 0
(E) = 50
(T) = 500 ms
DM 1110
DM 1111
DM 1112
DM 1113
DM 1114
DM 1115
DM 1116
DM 1117
DM 1118
DM 1119
DM 1120
DM 1150
DM 1151
DM 1100
DM 1101