Specifications
Section 2-1
2-1-4
Counting Speed
The maximum response pulse frequency of the High-speed Counter for offset
phase inputs is determined with the type of increment encoder connected to
the High-speed Counter. In this following example, OMRON’s E6B-CWZ3C
Encoder is connected to the High-speed Counter.
Example:E6B-CWZ3C (500 pulses/time)
Ratings
Clockwise (CW) Rotation
Phase A is advanced
1
⁄
4
±
1
⁄
8
T phase ahead of phase B.
Counterclockwise (CCW)
Rotation
Phase A is delayed
1
⁄
4
±
1
⁄
8
T phase behind phase B.
Item
Specification
Power supply voltage
5 VDC (–5%) to 12 V (+10%) with a peak-to-peak rip-
ple rate of 5% max.
Current consumption
50 mA max.
Resolution (P/R)
500
Output phases
Phase A, phase B, phase Z
Output type
Open collector output
Output capacity
Applied voltage: 30 VDC max.
Sink current: 80 mA max.
Residual voltage:
1 V max (when the sink current is 80 mA)
0.4 V max (when the sink current is 20 mA)
Max. response frequency
30 KHz
Output phase difference
A/B phase difference 90
°±
45
°
(
1
⁄
4
±
1
⁄
8
T)
Output rise/fall time
1.0
µ
s max. (Control output voltage 5 V, load resis-
tance 1 K
Ω
, cord length 50 cm)
Phase A
Phase B
CW direction
1
⁄
4
T
±
1
⁄
8
T (90
°±
45
°
)
1
⁄
4
T
±
1
⁄
8
T (90
°±
45
°
)
(360
°
)
CCW direction
Phase A
Phase B