22
Wiring Example of External Control Inputs
Section 3-5
Example 5: With Encoder
Conversion Adapter
In the following example, open collector outputs from an encoder is connected
as line driver inputs through the C500-AE001 Encoder Conversion Adapter.
Note
Connect the wires so that a counter input to the High-speed Counter Unit will
be turned ON when an output from the encoder is turned ON.
The C500-AE001 Encoder Conversion Adapter uses an Am26LS31-compati-
ble line driver. H will be output to the positive terminal and L will be output to
the negative terminal of the C500-AE001 when an input to the C500-AE001 is
H.
3-5
Wiring Example of External Control Inputs
In order to prevent chatter at the input, use solid-state as much as possible.
Counter input A
Counter input B
Counter input Z
Shielded, twisted-pair cable
Encoder
Shielded, twisted-pair cable
12-VDC12 VDC
power
supply
0 V
0 V
0 V
0 V
C500-AE001 Encoder
Conversion Adapter
Voltage
regulator
C200H-CT021 High-speed Counter Unit
External control input IN1
filter
filter
Sensor
Sensor output
Twisted-pair cable
Sensor
Sensor output
External control input IN2
12 or 24 V
12 or 24 V
12- to 24-VDC
power
supply
0 V
12 to 24 VDC