5.6.5.15.1 Auto reset
When programming High peak, Low peak, Time average, Gated timer and Totalize points, the system
allows an Auto reset function. If Auto reset is disabled, resettable points may only be reset manually.
If Auto reset is set up, the point being programmed will reset at programmed intervals, from once a
minute to once a month.
NOTE
: High peak, Low peak and Moving average points reset to the current value of the Basepoint.
Totalize points reset to zero.
To set the Auto reset function:
From the Reset control menu use the
UP (
↑↑↑↑↑
)
or
DOWN (
↓↓↓↓↓
)
button to highlight
Auto reset
and press
the
ENTER
button. The Auto reset Setup menu will be displayed with the following options:
Auto off
,
Daily
,
Weekly
, or
Monthly
.
a. Auto off
If the Auto reset is set to off, automatic reset of the programmed point will be disabled. Use the
UP (
↑↑↑↑↑
)
or
DOWN (
↓↓↓↓↓
)
button to highlight
Auto off
and press the
ENTER
button. Press the
EXIT
button to return to the Reset control menu.
b. Daily
When programming the Auto reset to Daily, the system will prompt for the start time and interval
for which that point will reset. The programmable start time is not necessarily the time at which
the first reset will occur. However, a reset will always occur at the start time every day. The actual
first reset depends upon the current time and the programmed interval. The Recorder calculates
the first reset by repeatedly adding the interval to the start time until the current time is met or
exceeded. See the example below:
Current Time:
07:30
Start Time:
09:15
Timed Interval:
1 Hour
09:15
Programmed Start Time
10:15
11:15
12:15
Note: The Interval (1 hour) added to the Start Time yields reset times.
.
23:15
00:15
01:15
.
07:15
07:30 (Current Time)
08:15
Time of the first reset for this example
To reset a point Daily:
Use the
UP (
↑↑↑↑↑
)
or
DOWN (
↓↓↓↓↓
)
button to highlight
Daily
and press the
ENTER
button. You will be
prompted with “start XX:XX:XX” The start time is entered in a 24-hour clock format in Hours (00
through 23), Minutes (00 through 59) and Seconds (00 through 59). This is the time the first reset
will begin. After the start time the point will reset at the interval rate.
If the start time is correct, press the
ENTER
or
YES
button to proceed to the interval. If the start
time is not correct, press the
NO
button. You will be prompted with “start hrs
Î
XX
Í
”. Use the
numeric keypad to enter the desired start hours (00 to 23) and press the
ENTER
button. You will
be prompted with “start mins
Î
XX
Í
”. Use the numeric keypad to enter the desired start minutes
(00 to 59) and press the
ENTER
button. You will be prompted with “start secs
Î
XX
Í
”. Use the