Appendix A – Configuring a 1-5Vdc input for a 0-250 psig pressure transducer
Page 3 of 6
Using the up/down arrow keys select
Output scale
and
touch
ENTER
.
You will now be prompted for the number of decimal places
that you would like to display and record. Using the up/
down arrow keys you can select 0, 1, 2, 3, 4, or 5decimal
places. For this example select 2 and touch
ENTER
.
You will now be prompted for the
hi
end of your output
scale. You should enter
250.00
and touch
ENTER
.
Another numeric keypad will appear prompting you for the
lo
end of your output scale. For this example (0-250 psig)
enter
0.00
and touch
ENTER
.
11.
12.
13.
14.
The numeric keypad will now prompt you for the
hi
end of
your input signal. For this example enter
5.00
and touch
ENTER
.
10.