![background image](http://html1.mh-extra.com/html/omega/rd8800/rd8800_user-manual_4055199147.webp)
Appendix E
Setting the Jumpers for the 3 or 6 Channel Mechanical or Solid State Relay
WARNING:
Due to hazardous voltages on the Rear Terminal Panel, use extreme caution when installing or
servicing your instrument. Please read the entire contents of the Installation and Wiring Chapter
before attempting to install or service your instrument.
WARNING:
Before attempting to remove the unit from the panel, opening the front or working on the back of
the instrument, ensure that the AC mains to the unit is
SWITCHED OFF
and
REMOVE THE
POWER CORD
from the socket on the rear panel. Ensure that all live connections to the rear
panel terminals are
ISOLATED
before removing the wiring.
Set Jumpers
The opto-isolated inputs require an external potential of 5 to 12 Volts DC @ 10mAmps by default. To activate the
inputs via potential free contacts (contact closure), jumpers need to be set as described below:
1. Remove the circuit board from the rear panel (See Figure 1).
2. Set the jumpers according to Table 1:
3. Screw the circuit board back onto the rear panel.
Figure 1 Jumper Location (Mechanical Relay shown - The jumpers
for the Solid State Relay are in the same location.)
Page 1 of 2
Mechanical Relay
(2010 Rev 1.0 and higher)
Solid State Relay
(2011 Rev 1.2 and higher)
P1 P2 P1 P2
Isolated Input
0-5 Vdc (Default)
Link
2 - 3
Link
2 - 3
Link
1 - 2
No Link
Non-Isolated
Contact Closure
Link
1 - 2
Link
1 - 2
Link
2 - 3
Link
1 - 2
P1 and P2 Jumper Location
NOTE:
Contact closure is non-
isolated from the System Ground
Table 1 Jumper Positions
Rear Panel
Circuit Board
3
2
1
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com