Maintenance / Checks
Monitoring the force limits
The operator control unit features a 2-processor safety system to monitor the force
limits. In an end position or after restarting, the integrated power disconnection is
tested automatically. During the monthly check of the door system, the force limits
need to be checked!
Check the force limits as described in chapter “Menu 5 + Menu 6: Force limits for
opening and closing” on page 61.
11
Cleaning / Care
If necessary, wipe the operator with a dry cloth.
NOTICE
For your safety, we recommend that the door system be checked
before initial use and as needed, but at least once a month. We
recommend consulting a specialist company.
Crush hazard at the door!
If the force limits are set too high, there is a risk of personal injury.
The factory setting is “6” for opening and “4” for closing.
•
The force on the main closure side must not exceed 400 N /
750 ms!
Hazardous voltage!
If the operator comes into contact with water, there is a risk of electric
shock!
•
Always pull the mains plug before working on the door or on the
operator!