NovoPort® IV
69
7.1
Restoring the factory settings
1.
Press the OPEN (B) and CLOSE (C) buttons at the same time.
2.
Press the buttons for approximately 3 seconds after you put the mains plug
into the mains socket.
7.2
Cycle counter
The cycle counter stores the number of OPEN/CLOSE actions powered by the
operator.
To read the meter, hold the button (C) at the control unit in for 3 seconds until you
see a figure.
The digital display shows the numbers starting from the highest to the lowest
decimal place consecutively. At the end, a horizontal line appears on the display,
for example: 3456 movements, 3 4 5 6 -
Motor standstill.
The motor does not rotate. Call a specialist company to repair
the motor.
Vacation lock is
activated.
Door does not open.
The side switch for SafeControl/Signal 112 is active.
A reset is required.
Wicket door contact test
failed.
Check the cables and clamping connections of the wicket door
contact.
Overload.
Remove external loads from terminal I.
Fault at the photoelectric
sensor.
Check the cables and clamping connections of the
photoelectric sensor.
Value
State
Diagnosis / remedy