Td (derivative
action time)
PID control parameters
Xp (gain)
Ti (integral
action time)
Control band
Assign default PID
parameters
T4
Controlled System
Heating Rate
Slow
Normal
Fast
Very fast
Operation
4‐38
P/N 213828_11
2014 Nordson Corporation
VersaBlue_PPA
Temperature Parameters
(contd.)
Controlled System Heating Rate
NOTE:
The setting
Normal
generally does not need to be changed. It cannot
be changed for grid and reservoir.
There are fixed parameter sets for the first four types.
Type
Suitable for
Slow*
Temperature channels that heat slowly
Normal
Grid, reservoir, hose, applicator
Fast **
Temperature channels that heat quickly
Very fast
Air heater
Customer
defined
Refer to
Parameters (Screen 3)
.
* To be set if heating the last 5 °C (9 °F) up to the setpoint takes too long
(possible with a very high temperature setpoint)
** To be set if the temperature swings above the setpoint during heatup
(possible with a very low temperature setpoint)
Normal
Parameters (Screen 3)
Controlled System Heating Rate: Customer defined
The PID control parameters can be selected as desired in this screen.
NOTE:
Should be adjusted only by personnel with experience in metrology
and control technology.
NOTE:
The I‐component can be deactivated with the value
0
.
The control band is the +/- range around the temperature setpoint. Above the
band the heater is always off, and below the band the heater is always on.
Recommended control band: 5 °C (9 °F)
Assign default PID
parameters
For orientation purposes, the parameter set of one of the
four controlled system heating rates can be loaded. Then individual values
can be adjusted.
Summary of Contents for VersaBlue VA
Page 12: ...Table of Contents X P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 28: ...Safety Instructions 1 14 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 40: ...Introduction 2 12 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 62: ...Installation 3 22 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 74: ...Operation 4 12 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 142: ...Operation 4 80 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 174: ...Maintenance 5 26 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 204: ...Troubleshooting 6 30 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 234: ...Repair 7 30 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 248: ...Password A 4 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...
Page 272: ...Glossary D 16 P N 213828_11 2014 Nordson Corporation VersaBlue_PPA...