System Settings
System I/O
Output
OLED User Interface
79
Part 1128351_02
E
2020
Nordson Corporation
Assigning Light Tower Outputs
1. Select
Output
press
>
then select
Light Tower.
2. Decide if you want to Invert (or reverse the polarity) of the Output. Select
Invert
and press
to change the polarity. The default, is not inverted
(active high).
3. Use the Up key on the Navigation pad to select
Assign
, then press
>
to
view the output menu list selection. Use the Up/Down keys on the
Navigation pad to scroll through the list. Press
to assign the output
selection you want. When done, press
<
to return to the Light Tower
menu.
4. Decide if you want to test the current output assignment. Select
Test
,
then press
to toggle Start/Stop the test.
5. Press
to return to the
Home
screen.
NOTES:
S
You can assign the same output selection to multiple outputs.
S
You can assign standard outputs using the Light Tower board.
S
The
System Alert
and
System Fault
outputs are inverted by default,
although the Invert check box is clear.
S
The default light tower output selections for the with the Legacy I/O
expansion kit are as follows:
‐
Output 1 through 7: Disabled
‐
Light Tower #2: System Fault
‐
Light Tower #3: Tank Low
S
The default light tower color associations are as follows:
‐
White - Power On/Off
‐
Green - System Ready
‐
Red - Any Fault Alarm or Flashing Red for any Stop Alarm
‐
Amber - Any Alert Alarm
‐
Blue - Idle condition (Setback, Heating, Pump Off, Ready Delay)
Summary of Contents for ProBlue Flex