NX5 OPERATION & MAINTENANCE MANUAL
OPERATING THE TRANSMITTER
PAGE 3.2.166
VERSION 0.1 2015-08-01
Remote Outputs - Remote AUI
Using the
Remote Outputs
Figure 3.2.152 on page 3.2.166
, you can configure up to 16
outputs that indicate either the presence of various alarms or the status of operator controlled circuits.
Nautel sets digital output defaults prior to shipping. See the NX5 Pre-installation Manual for details. If
necessary, re-configure the remote outputs as follows:
Figure 3.2.152: Remote I/O Page - Output Parameters
1.
On the left side of the page, select the desired remote output (1 through 16) from the list. Note:
you can configure remote outputs 1 through 16 for one of a variety of monitoring outputs.
2.
On the right side of the page, assign a name to the remote output by clicking
Channel
and
selecting one of the following options:
–
Not Assigned
- No alarm or status parameter is monitored.
–
Remote Enabled
- Active logic level indicates remote control is enabled (i.e., local plus remote).
Inactive logic level indicates the transmitter is in local control.
–
RF On/Off
- Active logic level indicates the transmitter’s RF power stage is on (enabled). Inactive logic
level indicates the transmitter’s RF power stage is off.
–
Active Exciter
- Active logic level indicates that exciter A is active. Inactive logic level indicates that
exciter B is active.
–
Auto Exciter Changeover Enable/Disable
- Active logic level indicates that the automatic
exciter changeover function is enabled. Inactive logic level indicates that the function is disabled.
Exit page
Outputs tab
Current
logic level