Ds230_03a_oi_e.doc / Jun-15
Page 14 / 100
5.1.
Power Supply
If the unit is connected to a DC power supply network, which supplies further devices or systems, it
must be ensured that no voltages
≥
60 V can occur at the terminals X3:1 and X3:2.
If this cannot be ensured, the unit must be supplied by a separate DC power pack, which may not be
connected to further devices or systems.
The requirements for both kinds of power supply are:
Nominal voltage range from 18 … 30 VDC
Ripple < 10% @ 24 V
External fuse (2.5 A, medium time lag) required
A separate power pack must cover the following requirements:
The switch-on current of the unit is maximum 2.5 A
The consumption of the unit is maximum 45 W
The 18 … 30 VDC power supply must be connected by the pluggable 2-pin screw terminal [X3].
The power supply input is protected by an internal reverse polarity protection.
pluggable 2-pin screw terminal [X3]
The input must be protected by an external fuse
(type and value see chapter
“Technical Specifications”).
A SIL3 certified power supply can be used without any further external
components or protections.