6.8.
„Operational Mode“ = 2
Mode
2
Sensor1
[X6 | SINCOS IN 1]
SinCos encoder
(SIN+, SIN-, COS+, COS-)
Sensor2
[X10 | CONTROL IN]
Incremental HTL encoder
(A) single channel
Control1
[X10 | CONTROL IN]
HTL/PNP control signal
(complementary)
Control2
Control signal input not available
Achievable
Safety Level
Speed
SIL3 / PLe
Direction
SIL3 / PLe ****
Standstill
SIL3 / PLe ****
**** A safety level can only be achieved in these cases, if it is physically ensured that
there only can be only one direction of rotary and linear movement. This can be realized for
example by using a self-locking gearbox.
This mode (only DS23x) allows to evaluate a dual channel system, equipped with two different
encoder types. Therefor a combination of a SinCos encoder and an incremental single channel HTL
encoder is used. The SinCos encoder must be performed in accordance to chapter
5.3
and the
incremental encoder to chapter
In this operational mode a DS230 variant reproduces always the input frequency at
[X6 | SINCOS IN 1] to the splitter output [X5 | SINCOS OUT].
A DS230 variant reproduces selectively the input frequency of Sensor1 or Sensor2 to the
splitter output [X4 | RS422 OUT].
The inputs at [X7 | SINCOS IN 2], [X8 | RS422 IN 1] and [X9 | RS422 IN 2] have no function.
When connecting the HTL encoder to terminal [X10] pin 4 and 5, the Control2 input is no
more available. In this case only the Control1 input can be used.
Summary of Contents for DS230 Series
Page 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Page 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Page 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Page 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...