Ds230_03a_oi_e.doc / Jun-15
Page 65 / 100
No.
Parameter
Range
Default
043
Switch Mode REL1
(switching condition for relay output)
:
0
|f| >= |Preselection|
Output switches in event of overspeed
{S, H}
1
|f| <= |Preselection|
Output switches in event of underspeed
{S, H, A}
2
|f| == |Preselection|
Output switches in event of leaving the
frequency band (Presel/- Hysteresis)
{S, H, A}
3
Standstill (see parameter 056)
Output switches in event of standstill
4
f >= Preselection
Output switches in event of overspeed
May only be used with positive preselection
values!
{S, H}
5
f <= Preselection
Output switches in event of underspeed
May only be used with positive preselection
values!
{S, H, A}
6
f == Preselection
Output switches in event of leaving the
frequency band (Presel/- Hysteresis)
Only used with positive preselection values!
{S, H, A}
7
f > 0
Output switches, if a positive frequency (e.g.
clockwise direction) is detected. The directional
information will be deleted immediately when
„standstill“(Parameter 056) is detected.
8
f < 0
Output switches, if a negative frequency (e.g.
anticlockwise direction) is detected. The
directional information will be deleted
immediately when „standstill“(Parameter 056)
is detected.
0 - 8
0
When using Switch Mode 2 or 6, a hysteresis is useful in order to avoid "bouncing" of
the outputs at the switching point.
When using Switch Mode 7 or 8, the specified standstill-time (see parameter 056) must
be higher than the adjusted wipe period (see parameter 044, ff.). This is helpful to
prevent a breakdown of the wipe signal before the wipe period has been elapsed.
With negative measuring values and presets a higher numerical value is smaller than
a lower numerical value, thus e. g. -1000 < -500.
Summary of Contents for DS230 Series
Page 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Page 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Page 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Page 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...