22 -
31
22. TROUBLE SHOOTING
3200
[SFC PARA. ERROR]
The parameter setting is illegal.
• Though Block 0 was set to "Automatic start" in
the SFC setting of the PLC parameter dialog box,
Block 0 does not exist.
■
Collateral informationmmon
• Common Information:File name
• Individual Information:Parameter number
■
Diagnostic Timing
• STOP
RUN
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnA
3201
[SFC PARA. ERROR]
The block parameter setting is illegal.
■
Collateral informationmmon
• Common Information:File name
• Individual Information:Parameter number
■
Diagnostic Timing
• STOP
RUN
3202
[SFC PARA. ERROR]
The number of step relays specified in the device
setting of the PLC parameter dialog box is less than
that used in the program.
■
Collateral informationmmon
• Common Information:File name
• Individual Information:Parameter number
■
Diagnostic Timing
• STOP
RUN
3203
[SFC PARA. ERROR]
The execution type of the SFC program specified in
the program setting of the PLC parameter dialog
box is other than scan execution.
■
Collateral informationmmon
• Common Information:File name
• Individual Information:Parameter number
■
Diagnostic Timing
• At power ON/At reset/STOP
RUN
Error
Code
Error Contents and Cause
Corrective Action
LED Status
CPU Status
Corresponding
CPU
*3
The diagnostic timing of CPU modules except for Universal QCPU can be performed only when switching the CPU modules to run.
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......