10 -
17
10. OTHER FUNCTIONS
(b) Methods using GPP function or a serial communication module
The remote PAUSE operation can be performed from GPP function or from a
serial communication module.
The operation using GPP function can be performed in the Remote operation of
the PLC menu in any mode.
The control using a serial communication module is performed with the
commands in the dedicated protocol.
For details on serial communication module control, refer to the Serial
Communication Module User's Manual.
1) When the END processing of the scan in which the remote PAUSE command
has received from GPP function is performed, the PAUSE status contact
(SM204) turns ON.
When performing up to the END instruction of the scan following the scan in
which the PAUSE status contact turned ON, the PAUSE status is established
and the operation is stopped.
2) When the remote RUN command is received from GPP function, the
sequence program operation is again performed from step 0.
Fig. 10.7 Time chart for PAUSE with GPP function
POINT
To arrange for outputs (Y) to be turned ON or OFF when the PAUSE status is
established, provide an interlock using the PAUSE state contact (SM204).
OFF
0
END
0
END
0
END
0
SM204
OFF
ON
RUN
PAUSE
ON
OFF
ON
Remote PAUSE
command
Remote RUN
command
RUN/STOP status
Comes ON
when the
PAUSE
condition
is satisfied
PAUSE status
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......