App -
95
APPENDICES
Table App. 3.11. Special register
ACPU
Special
Register
Special
Register
after
Conversion
Special
Register for
Modification
Name
Meaning
Details
Corresponding
CPU
D9000
SD1000
–
Fuse blown
Number of module
with blown fuse
• When fuse blown modules are detected, the first I/O number of the
lowest number of the detected modules is stored in hexadecimal.
(Example: When fuses of Y50 to 6F output modules have blown,
"50" is stored in hexadecimal)
To monitor the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1100 to SD1107 are reset to 0.)
• Fuse blow check is executed also to the output modules of remote
I/O stations.
QnA
D9001
SD1001
–
Fuse blown
Number of module
with blown fuse
• Stores the module numbers corresponding to setting switch
numbers or base slot numbers when fuse blow occurred.
• For the remote I/O station, the value of (module I/O No./10H) + 1 is
stored.
QnA
D9002
SD1002
–
I/O module
verify error
I/O module verify
error module number
• If I/O modules, of which data are different from data entered, are
detected when the power is turned on, the first I/O number of the
lowest number unit among the detected units is stored in
hexadecimal. (Storing method is the same as that of SD1000.)
To monitor the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1116 to SD1123 are reset to 0.)
• I/O module verify check is executed also to the modules of remote
I/O terminals.
QnA
D9004
SD1004
–
MINI link
master module
errors
Stores setting status
made at parameters
• Error status of the MINI(S3) link detected on loaded AJ71PT32(S3)
is stored.
QnA
D9005
SD1005
–
AC DOWN
counter
Number of times for
AC DOWN
• When the AC power supply module is used, 1 is added at
occurrence of an instantaneous power failure of within 20ms.
(The value is stored in BIN code.) It is reset when the power supply
is switched from OFF to ON.
QnA
• When the DC power supply module is used, 1 is added at
occurrence of an instantaneous power failure of within 1ms.
(The value is stored in BIN code.) It is reset when the power supply
is switched from OFF to ON.
QnA
D9008
SD1008
SD0
Self-diaghostic
error
Self-diaghostic error
number
• When error is found as a result of self-diagnosis, error number is
stored in BIN code.
QnA
AJ02 I/O module
Extension base unit
Setting
switch
Stored
data
Base unit
slot No.
Stored
data
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
b15
b8
b7
b0
Bits which correspond to faulty
AJ71PT32(S3) are turned on.
7th 6th 5th 4th 3rd2nd1st
8th
to
to
Bits which correspond to the signals of
AJ71PT32(S3), shown below, are
turned on as the signals are turned
on.
Hardware error (X0/X20)
MINI(S3) link error datection
(X6/X26)
MINI(S3) link
communication error
(X7/X27)
7th 6th 5th 4th 3rd 2nd1st
8th
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......