App -
64
APPENDICES
Table App. 2.10. Special relay
ACPU
Special
Relay
Special
Relay after
Conversion
Special
Relay for
Modification
Name
Meaning
Details
Corresponding
CPU
M9200
SM1200
–
ZNRD instruction
(LRDP instruction
for ACPU)
reception (for
master station)
OFF : Not accepted
ON
: Accepted
• Depends on whether or not the ZNRD (word device read)
instruction has been received.
• Used in the program as an interlock for the ZNRD
instruction.
• Use the RST instruction to reset.
QnA
M9201
SM1201
–
ZNRD instruction
(LRDP instruction
for ACPU)
completion (for
master station)
OFF : Not completed
ON
: End
• Depends on whether or not the ZNRD (word device read)
instruction execution is complete.
• Used as a condition contact for resetting M9200 and
M9201 after the ZNRD instruction is complete.
• Use the RST instruction to reset.
QnA
M9202
SM1202
–
ZNWR instruction
(LWTP instruction
for ACPU)
reception (for
master station)
OFF : Not accepted
ON
: Accepted
• Depends on whether or not the ZNWR (word device
write) instruction has been received.
• Used in the program as an interlock for the ZNWR
instruction.
• Use the RST instruction to reset.
QnA
M9203
SM1203
–
ZNWR instruction
(LWTP instruction
for ACPU)
completion (for
master station)
OFF : Not completed
ON
: End
• Depends on whether or not the ZNWR (word device
write) instruction execution is complete.
• Used as a condition contact to reset M9202 and M9203
after the ZNWR instruction is complete.
• Use the RST instruction to reset.
QnA
M9204
SM1204
–
ZNRD instruction
(LRDP instruction
for ACPU)
reception (for local
station)
OFF : Not completed
ON
: End
• On indicates that the ZNRD instruction is complete at the
local station.
QnA
M9205
SM1205
–
ZNWR instruction
(LWTP instruction
for ACPU) recep-
tion (for local
station)
OFF : Not completed
ON
: End
• On indicates that the ZNWR instruction is complete at the
local station.
QnA
M9206
SM1206
–
Host station link
parameter error
OFF : Normal
ON
: Abnormal
• Depends on whether or not the link parameter setting of
the host is valid.
QnA
M9207
SM1207
–
Link parameter
check results
OFF : Match
ON
: Mismatch
• Depends on whether or not the link parameter setting of
the master station in tier two matches that of the master
station in tier three in a three-tier system.
(Valid for only the master station in a three-tier system.)
QnA
M9208
SM1208
–
Sets master
station B and W
transmission range
(for lower link
master stations
only)
OFF : Transmits to tier2 and
tier 3
ON
: Transmits to tier2 only
• Depends on whether or not the B and W data controlled by
higher-link master station (host station) is sent to lower-
link local stations (tertiary stations).
When SM1208 is OFFB and W of host station is sent to
tertiary stations.
When SM1208 is ONB and W of host station is not sent to
tertiary stations.
QnA
M9209
SM1209
–
Link parameter
check command
(for lower link
master stations
only)
OFF : Executing the check
function
ON
: Check non-execution
• Set to ON not to match B and W of the higher and lower
links.
• When SM1209 is ON, the link parameters of the higher
and lower link are not checked.
• When SM1209 is OFF, the link parameters of the higher
and lower link are checked.
QnA
M9210
SM1210
–
Link card error (for
master station)
OFF : Normal
ON
: Abnormal
Control is performed depending on whether the link card
hardware is faulty or not.
QnA
M9211
SM1211
–
Link module error
(for local station
use)
OFF : Normal
ON
: Abnormal
Control is performed depending on whether the link card
hardware is faulty or not.
QnA
M9224
SM1224
–
Link status
OFF : Online
ON
: Offline,station-to-
station test, or self-
loopback test
Depends on whether the master station is online or offline or
is in station-to-station test or self-loopback test mode.
QnA
M9225
SM1225
–
Forward loop error
OFF : Normal
ON
: Abnormal
Depends on the error condition of the forward loop line.
QnA
M9226
SM1226
–
Reverse loop error
OFF : Normal
ON
: Abnormal
Depends on the error condition of the reverse loop line.
QnA
M9227
SM1227
–
Loop test status
OFF : Not being executed
ON
: Forward or reverse
loop test execution
underway
Depends on whether or not the master station is executing a
forward or a reverse loop test.
QnA
M9232
SM1232
–
Local station
operation status
OFF : RUN or STEP RUN
status
ON
: STOP or PAUSE
status
Control is performed depending on whether a local station is
in the STOP or PAUSE mode.
QnA
M9233
SM1233
–
Local station error
detect status
OFF : No errors
ON
: Error detection
Depends on whether or not a local station has detected an
error in another station.
QnA
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......