App -
51
APPENDICES
(2) System information
Table App. 2.3. Special relay
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM202
LED OFF command
OFF
ON : LED OFF
• When this relay goes from OFF to ON, the LEDs
corresponding to the individual bits at SD202 go off
U
New
QnA
SM203
STOP contact
STOP status
• Goes ON at STOP status
S (Status change)
M9042
QnA
SM204
PAUSE contact
PAUSE status
• Goes ON at PAUSE status
S (Status change)
M9041
QnA
SM205
STEP-RUN contact
STEP-RUN status
• Goes ON at STEP-RUN status
S (Status change)
M9054
QnA
SM206
PAUSE enable coil
OFF : PAUSE disabled
ON
: PAUSE enabled
• PAUSE status is entered if this relay is ON when the
PAUSE contact goes ON
U
M9040
QnA
SM210
Clock data set request
OFF : Ignored
ON
: Set request
• When this relay goes from OFF to ON and after END
instruction execution of subsequent scan, clock data
stored in SD210 to SD213 are written to the CPU
module.
U
M9025
QnA
SM211
Clock data error
OFF : No error
ON
: Error
• ON when error is generated in clock data (SD210 to
SD213) value, and OFF if no error is detected.
S (Request)
M9026
QnA
SM212
Clock data display
OFF : Ignored
ON
: Display
• Displays clock data as month, day, hour, minute, and
second at the LED display at front of CPU
module.(Enabled only for Q3ACPU and Q4ACPU)
U
M9027
Q3A
Q4A
Q4AR
SM213
Clock data read
request
OFF : Ignored
ON
: Read request
• When this relay is ON, clock data is read to SD210 to
SD213 as BCD values.
U
M9028
QnA
SM250
Max. loaded I/O read
OFF : Ignored
ON
: Read
• When this relay goes from OFF to ON, maximum
loaded I/O number is read to SD250.
U
New
QnA
SM251
I/O change flag
OFF : No replacement
ON
: Replacement
• By turning this relay ON after setting the head I/O
number of the replaced I/O module to SD251, the I/O
module can be replaced online (with power on).
(Only one module can be replaced for each setting.)
• Turn this relay ON in the test mode of the program or
peripheral device for an I/O module change during
RUN, or in the test mode of the peripheral device for
an I/O change during STOP.
• Do not execute a RUN/STOP mode change until I/O
module change is finished.
U
M9094
Q2A(S1)
Q3A
Q4A
Q4AR
SM252
I/O change OK
OFF : Replacement
prohibited
ON
: Replacement enabled
• Goes ON when I/O replacement is OK.
S (END)
New
SM255
MELSECNET/10
module 1 information
OFF : Operative network
ON
: Standby network
• Goes ON for standby network(If no designation has
been made concerning active or standby, active is
assumed.)
S (Initial)
New
QnA
SM256
OFF : Reads
ON
: Does not read
• For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
U
New
SM257
OFF : Writes
ON
: Does not write
• For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
U
New
SM260
MELSECNET/10
module 2 information
OFF : Operative network
ON
: Standby network
• Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial)
New
QnA
SM261
OFF : Reads
ON
: Does not read
• For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
U
New
SM262
OFF : Writes
ON
: Does not write
• For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
U
New
SM265
MELSECNET/10
module 3 information
OFF : Operative network
ON
: Standby network
• Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial)
New
QnA
SM266
OFF : Reads
ON
: Does not read
• For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
U
New
SM267
OFF : Writes
ON
: Does not write
• For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
U
New
SM270
MELSECNET/10
module 4 information
OFF : Operative network
ON
: Standby network
• Goes ON for standby network
(If no designation has been made concerning active
or standby, active is assumed.)
S (Initial)
New
QnA
SM271
OFF : Reads
ON
: Does not read
• For refresh from link to CPU module (B, W, etc.)
indicate whether to read from the link module.
U
New
SM272
OFF : Writes
ON
: Does not write
• For refresh from CPU module to link (B, W, etc.),
designate whether to write to the link module.
U
New
SM280
CC-Link error
OFF : Normal
ON
: Error
• Goes ON when a CC-Link error is detected in any of
the installed CC-Link module. Remains ON if the
condition is restored to normal thereafter.
S (Error)
New
QnA
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......