19. LOADING AND INSTALLATION
(3) Grounding
(a) Carry out the independent grounding if possible.
(b) If independent grounding is impossible, carry out the shared grounding (2) as
shown below.
(c) Use the cable of 2mm
2
or more for grounding.
Set the grounding point closer to the PLC to make the grounding cable short as
possible.
(d) If any malfunction occurs due to grounding, disconnect either or both of the LG
and FG terminals of the base unit from the ground.
CAUTION
Always ground the FG and LG terminals to the protective ground conductor.
Failure to do so may cause an electric shock or malfunctions.
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
(1) Independent grounding ... Best
(2) Joint grounding ... Good
(3) Joint grounding ... Not allowed
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......