22 -
21
22. TROUBLE SHOOTING
1510
[DUAL DC DOWN 5V]
The power supply voltage (100 to 240VAC) of
either of the two power supply modules on the
power supply duplexing extension base unit
dropped to or below 85% of the rated voltage.
(This can be detected from the control system of
the redundant system.)
■
Collateral informationmmon
• Common Information:–
• Individual Information:–
■
Diagnostic Timing
• Always
Check the supply voltage of the power supply
module. If the voltage is abnormal then replace the
power supply module.
RUN:
On
ERR.:
On
CPU Status:
Continue
Q4AR
1520
[DC DOWN 5V]
The voltage(100 to 240VAC) of the power supply
module on the extension base unit dropped to or
below 85% of the rated voltage.
(This can be detected from the control system of
the stand-alone system or redundant system.)
■
Collateral informationmmon
• Common Information:–
• Individual Information:–
■
Diagnostic Timing
• Always
Check the supply voltage of the power supply
module. If the voltage is abnormal then replace the
power supply module.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
1530
[DC DOWN 24V]
The 24 VDC power supplied to the system
management module AS92R has dropped below
90% of the rated voltage.
(This can be detected from the control system or
standby system of the redundant system.)
■
Collateral informationmmon
• Common Information:–
• Individual Information:–
■
Diagnostic Timing
• Always
Check the 24VDC power supplied to the system
management module AS92R.
RUN:
On
ERR.:
On
CPU Status:
Continue
1600
[BATTERY ERROR
*2
]
• The battery voltage in the CPU module has
dropped below stipulated level.
• The lead connector of the CPU module battery is
not connected.
■
Collateral informationmmon
• Common Information:Drive Name
• Individual Information:–
■
Diagnostic Timing
• Always
• Change the battery.
• If the battery is for program memory, standard
RAM or for the back-up power function, install a
lead connector.
RUN:
On
ERR.:
Off
CPU Status:
Continue
QnA
1601
[BATTERY ERROR
*2
]
Voltage of the battery on memory card 1 has
dropped below stipulated level.
■
Collateral informationmmon
• Common Information:Drive Name
• Individual Information:–
■
Diagnostic Timing
• Always
Change the battery.
1602
[BATTERY ERROR
*2
]
Voltage of the battery on memory card 2 has
dropped below stipulated level.
■
Collateral informationmmon
• Common Information:Drive Name
• Individual Information:–
■
Diagnostic Timing
• Always
Change the battery.
RUN:
On
ERR.:
On
CPU Status:
Continue
Error
Code
Error Contents and Cause
Corrective Action
LED Status
CPU Status
Corresponding
CPU
*2
The BAT.ALM LED turns on at BATTERY ERROR.
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......