22 -
35
22. TROUBLE SHOOTING
4201
[FOR NEXT ERROR]
A NEXT instruction was executed although no FOR
instruction has been executed.
Alternatively, there are more NEXT instructions
than FOR instructions.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnA
4202
[FOR NEXT ERROR]
More than 16 nesting levels are programmed.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
Keep nesting levels at 16 or under.
4203
[FOR NEXT ERROR]
A BREAK instruction was executed although no
FOR instruction has been executed prior to that.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
4210
[CAN'T EXECUTE(P)]
The CALL instruction is executed, but there is no
subroutine at the specified pointer.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
4211
[CAN'T EXECUTE(P)]
There was no RET instruction in the executed
subroutine program.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
4212
[CAN'T EXECUTE(P)]
The RET instruction exists before the FEND
instruction of the main routine program.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
4213
[CAN'T EXECUTE(P)]
More than 16 nesting levels are programmed.
■
Collateral informationmmon
• Common Information:Program error location
• Individual Information:–
■
Diagnostic Timing
• When instruction executed
Keep nesting levels at 16 or under.
Error
Code
Error Contents and Cause
Corrective Action
LED Status
CPU Status
Corresponding
CPU
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......