20. EMC AND LOW VOLTAGE DIRECTIVES
(c) Always use double-shielded coaxial cables as the coaxial cables
*2
connected to
the 10BASE2 connectors. Ground the double-shielded coaxial cable by
connecting its outer shield to the ground.
Refer to (1) for the grounding of the shield.
*2
Make sure to attach a ferrite core to the cable.
As a ferrite core, ZCAT2035 manufactured by TDK is recommended.
(4) I/O signal cables and other communication cables
Always ground the I/O signal lines (including common line) and other communication
cables (RS-232-C, RS-422, etc.) in the same manner as described in (1) if they are
brought out of the control panel.
(5) Positioning modules
Precautions for configuring machinery compliant with the EMC Directives using the
AD75P -S3 are described below.
(a) When using a cable of 2m (6.56ft.) or less
• Ground the shield section of the external wiring cable with a cable clamp.
(Ground the shield at the closest location to the AD75 external wiring
connector.)
• Connect the external wiring cable to a drive unit or an external device in the
shortest distance.
• Install the drive unit in the same panel.
Ethernet is the registered trademark of XEROX, Co.,LTD
Power supply module
CPU module
AD
75
External wiring connector
Cable clamp
External wiring cable
(within 2m (6.56ft.))
Drive unit
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......