17.
17 -
1
BASE UNIT AND EXTENSION CABLE
17
BASE UNIT AND EXTENSION CABLE
This section explains the specifications of the base units (the main and extension base
units) and extension cables available for the systems, and the application standards for
use of extension base units.
17.1 Specifications of Base Units
(1) Main base unit specifications
(2) Extension base unit specifications
*1
1 For the attachment of the dustproof cover, refer to Section 19.6.
Item
Model Name
A32B
A32B-S1
A35B
A38B/A38HB/A38HBEU
I/O module
installation range
2 modules can be installed.
5 modules can be
installed.
8 modules can be
installed.
Extension possibility
Not extendable
Extendable
Extendable
Extendable
Installation hole size
6 bell-shaped holes (for M5 screws)
External dimensions
247mm (9.6inch) 250mm
(9.8inch) 29mm
(1.1inch)
268mm (10.5inch) 250mm
(9.8inch) 29mm
(1.1inch)
382mm (14.9inch) 250mm
(9.8inch) 29mm (1.1inch)
480mm (18.7inch) 250mm
(9.8inch) 29mm
(1.1inch)
Weight
0.96kg
1.3kg
1.5kg
1.9kg
Item
Model Name
A62B
A65B
A68B
A52B
A55B
A58B
I/O module
installation range
2 modules can
be installed.
5 modules can
be installed.
8 modules can
be installed.
2 modules can
be installed.
5 modules can
be installed.
8 modules can
be installed.
Power supply module
loading
Power supply module required
Not required. (See
.)
Installation hole size
6 bell-shaped holes (for M5 screws)
6 bell-shaped holes (for M5 screws)
Terminal screw size
–
M4 0.7 6 (FG terminal)
Applicable wire size
–
0.75 to 2mm
2
Applicable solderless
terminal
–
(V)1.25-4, (V)1.25-YS4, (V)2-YS4A
Applicable tightening torque: 78 to 118N cm
External dimensions
283mm (11.0inch)
250mm (9.8inch)
29mm (1.1inch)
352mm (13.7inch)
250mm (9.8inch)
29mm (1.1inch)
466mm (18.2inch)
250mm (9.8inch)
29mm (1.1inch)
183mm (7.1inch)
250mm (9.8inch)
29mm (1.1inch)
297mm (11.6inch)
250mm (9.8inch)
29mm (1.1inch)
411mm (16.0inch)
250mm (9.8inch)
29mm (1.1inch)
Weight
1.1kg
1.4kg
1.9kg
1.0kg
1.2kg
1.7kg
Accessory
–
*1
Dustproof cover (for I/O module): 1 pc.
POINT
Summary of Contents for Q2ACPU
Page 1: ......
Page 2: ......
Page 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Page 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Page 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Page 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Page 357: ...22 12 22 TROUBLESHOOTING ...
Page 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Page 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Page 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Page 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Page 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Page 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Page 567: ...MEMO ...
Page 569: ......
Page 570: ......