IX
Test Run Mode ]
- 119 -
HWE10190
GB
2. 2-unit
combination
(1) Cooling operation
Specifications
Indoor unit
model
PFAV-P500VM-E
Outdoor unit
model
PUHY-P500YSJM-A
PUHY-P250YJM-A
PUHY-P250YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
Outdoor
35°C/- [95°F/-]
Piping
Main pipe
m[ft]
7.5 [24-1/4]
Refrigerant charge
kg
[lbs-oz]
22.5 [49-10]
Outdoor
unit
Electric current
A
26.7
Voltage
V
400
Compressor frequency
Hz
65
65
LEV open-
ing
Indoor unit
Pulse
387
SC(LEV1)
100
100
LEV2
2100
2100
Pressure
High pressure (after O/S)/Low
pressure (before accumulator)
MPa
[psi]
3.11/0.86 [451/125]
3.11/0.86 [451/125]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
85 [185]
85 [185]
Heat exchanger out-
let (TH3)
47 [117]
47 [117]
Accumulator inlet
7 [45]
7 [45]
Accumulator outlet
7 [45]
7 [45]
SCC outlet (TH6)
27 [81]
27 [81]
Compressor suction
19 [60]
19 [66]
Compressor shell
bottom
38 [100]
38 [100]
Indoor
unit
LEV inlet
19 [66]
Heat exchanger out-
let
6 [43]
0000002115.book 119 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......