- 26 -
[
II
Restrictions ]
GB
HWE10190
[5] An Example of a System to which an MA Remote Controller is connected
1. Single-outdoor-unit system (manual IC/OC address setup)
(1) Sample control cable wiring configuration
(2) Cautions
1) Do not connect terminal blocks TB5 on the indoor units
that are connected to an outdoor unit in a different refrig-
erant circuit with each other.
2) No more than two MA remote controllers can be connect-
ed to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Maximum cable distance (1.25 mm
2
[AWG16] min.)
L1
≤
200m [656ft]
2) Transmission cable for the centralized control system
No connection is required.
3) MA remote controller wiring
Total cable length (0.3 to 1.25mm
2
[AWG22 to 16])
m1
≤
200m [656ft]
m2+m3
≤
200m [656ft]
IC
TB5
M1 M2 S
TB15
1 2
01
A B
MA (main body)
IC
TB5
M1 M2 S
1 2
TB15
02
A B
MA (sold separately)
A B
MA (main body)
Main
Sub
Group
Group
A B
MA
m1
m3
m2
L1
OC
TB3
TB7
M1 M2
M1 M2 S
51
OC
TB3
TB7
M1 M2
M1 M2 S
52
0000002115.book 26 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......