[1] System configuration
1. Unit
combination
The table below shows a list of outdoor units that are compatible with the indoor unit described in this manual.
(1) Standard type combination
(2) Fresh Air Intake type combination
1) Do not connect the PFAV series indoor units and other types of indoor units together to an outdoor unit.
[2] Types and Maximum allowable Length of Cables
1. Wiring
work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man-
ual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference.
(Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic compo-
nents on the terminal block.
6) Use 2-core shielded cables as transmission cables.
Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
(2) Control wiring
Different types of control wiring are used for different systems.
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line.
Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce
noise interference.
Indoor unit model name
Outdoor unit model name
PFAV-P250VM-E
PUHY-P250YJM-A
PFAV-P500VM-E
PUHY-P500YSJM-A
PFAV-P750VM-E
PUHY-P750YSJM-A
Indoor unit model name
Outdoor unit model name
PFAV-P300VM-E-F
PUHY-P250YJM-A
PFAV-P600VM-E-F
PUHY-P500YSJM-A
PFAV-P900VM-E-F
PUHY-P750YSJM-A
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
TB
3
TB
7
Outdoor unit
Indoor unit
Remote Controller
2-core shielded cable
Outdoor unit
multiple-core cable
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
2-core shielded cable
Indoor unit
Remote Controller
0000002115.book 17 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......