[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical
property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a con-
fined area.
*1 When CFC11 is used as a reference
*2 When CO
2
is used as a reference
2. Refrigerant
composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To
be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn
out, the composition of the remaining refrigerant will change and become unsuitable for use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure
characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
New Refrigerant (HFC type)
Conventional Refriger-
ant (HCFC type)
R410A
R407C
R22
R32/R125
R32/R125/R134a
R22
Composition (wt%)
(50/50)
(23/25/52)
(100)
Type of Refrigerant
Pseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
Chloride
Not included
Not included
Included
Safety Class
A1/A1
A1/A1
A1
Molecular Weight
72.6
86.2
86.5
Boiling Point (°C/°F)
-51.4/-60.5
-43.6/-46.4
-40.8/-41.4
Steam Pressure
(25°C,MPa/77°F,psi) (gauge)
1.557/226
0.9177/133
0.94/136
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.0
42.5
44.4
Flammability
Nonflammable
Nonflammable
Nonflammable
Ozone Depletion Coefficient (ODP)
*1
0
0
0.055
Global Warming Coefficient (GWP)
*2
1730
1530
1700
Refrigerant Charging Method
Refrigerant charging in
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
Replenishment of Refrigerant after a Refrigerant
Leak
Available
Available
Available
Temperature (°C/°F)
Pressure (gauge)
R410A
R407C
R22
MPa/psi
MPa/psi
MPa/psi
-20/-4
0.30/44
0.18/26
0.14/20
0/32
0.70/102
0.47/68
0.40/58
20/68
1.34/194
0.94/136
0.81/117
40/104
2.31/335
1.44/209
1.44/209
60/140
3.73/541
2.44/354
2.33/338
65/149
4.17/605
2.75/399
2.60/377
0000002115.book 13 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......