X
Troubleshooting ]
- 150 -
HWE10190
GB
1. Error
Code
ACCT sensor fault (Detail code 115)
2. Error
definition and error detection method
When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
Refer to section -6-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 202)
1. Error
Code
ACCT sensor circuit fault (Detail code 117)
2. Error
definition and error detection method
When an error value is detected with the ACCT detection circuit just before the inverter starts
3. Cause, check method and remedy
Refer to section -6-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 202)
5301
Cause
Check method and remedy
(1)
Inverter open output phase
Check the output wiring connections.
(2)
Compressor failure
Refer to X [4] -6- (2) [2].(page 204)
(3)
INV board failure
Refer to X [4] -6- (2) [1],[3],[4].(page 204)
5301
Cause
Check method and remedy
(1)
INV board failure
Refer to X [4] -6- (2) [1],[3],[4].(page 204)
(2)
Compressor failure
Refer to X [4] -6- (2) [2].(page 204)
0000002115.book 150 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......