X
Troubleshooting ]
- 177 -
HWE10190
GB
In the case of MA remote controller
2. Phenomena
When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off,
and the display lights out immediately, and the unit stops.
(1) Cause
1) The power for the M-NET transmission line is not supplied from the outdoor unit.
2) Short circuit of the transmission line.
3) Incorrect wiring of the M-NETtransmission line on the outdoorunit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit.
4) Disconnected M-NET transmission line on the indoor unit side.
5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or
disconnected connector.
(2) Check method and remedy
1)
When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
See Section X [4] -7- (2) Troubleshooting transmission power circuit of outdoor unit for how to check the items in Section 1 in the
flowchart above.(page 210)
YES
YES
YES
YES
NO
NO
NO
NO
Same symptom for all units in a
system with one outdoor unit?
Check the
self-diagnosis LED
Check 1).
Check for
2) and 3).
Check 4).
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
17 - 30V?
Check 5).
Error found?
Indoor unit board or
MA remote controller failure
Correct
the error.
Correct the error.
Is the error code 7102
displayed?
0000002115.book 177 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......