(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the
INV board er-
ror detection
circuit.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Overcurrent error
(4250 Detail code No. 101, 104,
105, 106, and 107)
Replace the INV board.
(2)
Put the outdoor unit
into operation.
2)
Logic error
(4220 Detail code No. 111)
Replace the INV board.
3)
ACCT sensor circuit failure
(5301 Detail code No.117)
Replace the INV board.
4)
IPM open
(5301 Detail code No.119)
Normal
[2]
Check for
compressor
ground fault
or coil error.
Disconnect the compressor
wiring, and check the com-
pressor Meg, and coil resis-
tance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
Check that there is no liquid re-
frigerant in the compressor.
If there is none, replace the com-
pressor.
2)
Compressor coil resistance failure
Coil resistance value of 0.71 ohm
(20°C [68°F]):P250 model
Coil resistance value of 0.32 ohm
(20°C [68°F]): P350, P400 models
Replace the compressor.
0000002115.book 204 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......