- 30 -
[
II
Restrictions ]
GB
HWE10190
3. Group operation of the indoor units connected to different outdoor units
(1) Sample control cable wiring configuration
(2) Cautions
1) Assign sequential addresses to the indoor unit.
2) Do not connect the terminal blocks (TB5) of the indoor
units that are connected to different outdoor units with
each other.
3) No more than two MA remote controllers can be connect-
ed to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
When a relay connector for MA remote controller cable is
removed from the indoor unit, the unit can be in the same
state as when MA remote controller is removed from the
unit.
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Same as section [5] 1.
2) Transmission cable for the centralized control system
Same as section [5] 1.
3) MA remote controller wiring
Total cable length (0.3 to 1.25mm
2
[AWG22 to 16])
m1+m2+m3
≤
200m [656ft]
m1
m2
m3
M1 M2
M1 M2
M1M2
M1 M2
M1 M2
M1 M2
S
S
1 2
Leave the power jumper
as it is on CN41.
Leave the power jumper
as it is on CN41.
MA (main body)
Sub
MA (main body)
Main
Group
L1
L2
TB3
TB7
51
OC
IC
01
TB15
TB5
A B
A B
OC
TB3
TB7
52
IC
02
TB15
TB5
0000002115.book 30 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......