IX
Test Run Mode ]
- 118 -
HWE10190
GB
(2) Heating operation
Specifications
Indoor unit
model
PFAV-P250VM-E
PFAV-P300VM-E-F
Outdoor unit
model
PUHY-P250YJM-A
PUHY-P250YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/- [68°F/-]
7°C/- [45°F/-]
Outdoor
7°C/6°C [45°F/43°F]
7°C/3°C [45°F/37°F]
Piping
Main pipe
m[ft]
7.5 [24-1/4]
7.5 [24-1/4]
Refrigerant charge
kg
[lbs-oz]
11.5 [25-6]
11.5 [25-6]
Outdoor
unit
Electric current
A
12.5
13.5
Voltage
V
400
400
Compressor frequency
Hz
71
71
LEV open-
ing
Indoor unit
Pulse
406
708
SC(LEV1)
0
0
LEV2
2100
2100
Pressure
High pressure (after O/S)/Low
pressure (before accumulator)
MPa
[psi]
2.85/0.61 [413/88]
2.65/0.58 [384/84]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
82 [180]
75 [167]
Heat exchanger outlet
(TH3)
0 [32]
2 [36]
Accumulator inlet
-2 [28]
0 [32]
Accumulator outlet
-2 [28]
0 [32]
Compressor suction
-2 [28]
0 [32]
Compressor shell bot-
tom
40 [104]
23 [73]
Indoor
unit
LEV inlet
38 [100]
30 [86]
Heat exchanger outlet
80 [176]
70 [158]
0000002115.book 118 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......