IX
Test Run Mode ]
- 113 -
HWE10190
GB
(2) Example: PUHY-P500YSHM-A
(3) Sample calculation
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
[3/4"][98 ft]
[3/8"]
[3 ft]
[3/8"]
[9 ft]
15.88 (30 m)
9.52
(3 m)
9.52
(1 m)
Liquid
separator
Liquid
separator
P600-F
P600-F
All the pipes in the figure are liquid pipes.
15.88 : 30 m = 30 m
9.52 : 3 m + 1m = 4 m
According to the above formula
The calculation result would be 11.24, and it is rounded up to the nearest 0.1.
The final result will be as follows:
Amount of refrigerant to be charged (kg) = (0.2 X 30) + (0.06 X 4) + 5.0 = 11.24kg
Amount of refrigerant to be charged = 11.3kg
All the pipes in the figure are liquid pipes.
[3/4"] : [98 ft] = [98 ft]
[3/8"] : [9 ft] + [3 ft] = [12 ft]
According to the above formula
The calculation result would be 395.5 oz, and it is rounded up to the nearest 1 oz.
The final result will be as follows:
Amount of refrigerant to be charged (oz) = (2.15 X 98) + (0.65 X 12) + 177 = 395.5oz
Amount of refrigerant to be charged = 396 oz
0000002115.book 113 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......