VIII
Control ]
- 90 -
HWE10190
GB
(2) Dipswitches (Fresh Air Intake type)
1) SW1,3,7,8
1) The setting timings for the dipswitches 1 and 3 is when the units are stopped (remote controller is switched off). Power reset
is not required.
2) The settings in the shaded areas indicate factory settings.
Switch
Function
Function according to switch setting
Switch setting
timing
Notes
OFF
ON
OFF
ON
SW1
1
Room temperature detec-
tion position
Indoor unit return air
Built-in sensor on the re-
mote controller
2
Filter sign
When the unit is
stopped (remote
controller is
switched off)
3
4
-
-
-
5
Remote display option
Fan output
Thermo-ON signal
6
-
-
-
7
Forced heating operation
Disabled
Enabled
When this switch is set to ON,
units are forced to operate in
the heating mode when the
return air dry temperature is at
or below 5°C[41°F].
8
-
-
-
9
Automatic recovery after
power failure
Disabled
Enabled
Set these switches to OFF
when SWC is set to ON.
10
Power reset
Disabled
Enabled
SW3
1
Model setting
Heat pump
Cooling-only
2
Capacity code
Refer to the table on the setting combination with
SW2.
3
Forced Thermo-ON
Disabled
Forced Thermo-ON
Return air temp. and preset
temp. are fixed.
4
Indoor unit fan operation
during defrost cycle
OFF
ON
5
-
-
-
6
Heat dissipation
1 min. (heating only)
3 min. 5 sec. (regardless
of the operation mode)
7
Automatic LEV value con-
version function
Not available
Available
8
Negative 4°C [7.2°F] off-
set (heating)
Enabled
Disabled
Set this switch to ON (dis-
abled) on the floor-standing
models.
9
-
-
-
Factory settings for these
switches depend on the unit
capacity. Refer to section 2).
10
-
-
-
SW7
1
-
-
-
2
Temp. value used to con-
trol indoor temp.
Return air temp.
Supply air temp.
When indoor and
outdoor units are
switched off
3
-
-
-
4
-
-
-
When the unit is
stopped (remote
controller is
switched off)
SW8
1
-
-
-
2
-
-
-
3
-
-
-
F i l t e r s i g n
1 0 0 h
O F F
O F F
S W 1 - 2
S W 1 - 3
O N
O F F
O F F
O N
O N
O N
1 2 5 0 h
N / A
2 5 0 0 h
P 3 0 0 , P 6 0 0
O N
O F F
S W 1 - 2
S W 1 - 3
O F F
O N
P 9 0 0
Factory setting
0000002115.book 90 ページ 2011年6月4日 土曜日 午前10時48分
Summary of Contents for PUHY-P250YJM-A
Page 1: ......
Page 11: ... 2 HWE10190 GB ...
Page 25: ... 16 HWE10190 GB ...
Page 45: ... II Restrictions 36 HWE10190 GB ...
Page 47: ... 38 HWE10190 GB ...
Page 57: ... 48 HWE10190 GB ...
Page 69: ... IV Indoor Unit Components 60 HWE10190 GB ...
Page 71: ... 62 HWE10190 GB ...
Page 73: ... V Remote Controller 64 HWE10190 GB ...
Page 75: ... 66 HWE10190 GB ...
Page 83: ... 74 HWE10190 GB ...
Page 91: ... VII Refrigerant Circuit 82 HWE10190 GB ...
Page 93: ... 84 HWE10190 GB ...
Page 115: ... VIII Control 106 HWE10190 GB ...
Page 117: ... 108 HWE10190 GB ...
Page 137: ... 128 HWE10190 GB ...
Page 225: ... X Troubleshooting 216 HWE10190 GB ...
Page 227: ... 218 HWE10190 GB ...
Page 272: ......